High-Energy MOV Primary Stage Protection for both Line-to-Line and Line-to-Ground
All-Mode protection including both Phase-to-Phase and Phase-to-Ground
Equipped with 3/4" Conduit Offset Nipple for easy mounting to a Service Entrance Panel
Electrical Specifications
208 VAC (Phase-to-Phase) Protection Levels
Maximum No Conduction AC Voltage = 280 Vrms
Maximum 1mA Conduction Voltage = 396 Vrms
Maximum single pulse energy = 1,200 Joules
Maximum single pulse current = 70,000 Amperes
Clamping evel = 720 Volt peak @ 500 Amperes
120 VAC (Phase-to-Ground) Protection Levels
Maximum No Conduction AC Voltage = 140 Vrms
Maximum 1mA Conduction Voltage = 198 Vrms
Maximum single pulse energy = 600 Joules
Maximum single pulse current = 70,000 Amperes
Clamping evel = 360 Volt peak @ 500 Amperes
Mechanical & Temperature Specifications:
Length = 5 in.
Width = 5 in.
Depth = 4 in.
Weight = 1 lb.
Equipped with 3/4" Conduit Offset Nipple for easy mounting to a Service Entrance Panel
Operating Temperature Range: -40 to +70°C
Dimensions:
Functional Wiring Diagram:
Summary:
This unit is designed to protect a standard 120/208VAC 3-phase WYE configurations (center grounded), AC power feeder. This unit will protect in all modes. That is,
differential protection Phase-to-Phase and also each Phase-to-Ground. This is a primary stage protector and would be connected at the Breaker /
Distribution Panel before the power is distributed throughout the Signal House or Case.